Interactive 3D course

How an FM-200 system puts out a fire

Six short scenarios, each with one quick question. Watch it play, or step through at your own pace.

1 / 14Overview
Loading the 3D room…

Drag to look around. Tap a part for details.

    The server room

    FM-200 puts fires out without water or residue.

    Drag to look around. Tap a part for details.

    For learning only. Delays, hold and abort behaviour, concentrations and cylinder sizes depend on each room and panel setting, and are set by a design to NFPA 2001 / ISO 14520 / EN 12094.

    How an FM-200 clean agent system works

    An FM-200 system is a clean agent fire suppression system. Smoke detectors in two zones confirm the fire, the control panel sounds the alarms, seals the room and runs a short countdown, then releases HFC-227ea gas from cylinders. In 10 seconds or less the gas reaches about 7–8.5 % and puts the fire out by absorbing its heat, with no water and no residue.

    01

    Detection

    Ceiling smoke detectors are wired in two separate zones. When the first zone sees smoke, the panel rings the bell and warns staff. No gas is ever released on one detector alone.

    02

    Confirmation

    When a detector in the second zone also sees smoke, the panel treats the fire as real and starts the release sequence. This is called coincidence detection. The manual release button on the panel, outside the room, can start the same sequence.

    03

    Warning and sealing

    A sounder and a flashing beacon tell everyone to leave and to keep out. The panel stops the air conditioning and closes the dampers and the door, so the gas stays in the room.

    04

    Countdown

    A pre-discharge delay, usually 30 seconds, gives people time to get out. The hold-off button by the exit pauses it only while it is pressed, so it is held until the panel is keyed to MANUAL ONLY. With the key switch on MANUAL ONLY, automatic release is blocked while people work inside.

    05

    Release

    At zero the panel fires the actuator on the main cylinder; the connected reserve cylinder stays full. Nitrogen at 25 bar pushes the liquid agent through the pipework to the nozzles, where it turns into gas.

    06

    Extinguishing and hold time

    The discharge is over in 10 seconds or less. At its design concentration the agent absorbs heat from the flame and stops combustion. A pressure switch lights "gas released" at the door, and the sealed room keeps the concentration for about 10 minutes.

    07

    After the fire

    Keep the door shut until the hold time ends. Then ventilate, find the cause and reset the panel. The panel's MAIN / RESERVE key puts the reserve cylinder on duty while the main one is refilled. Servers and documents are left clean and dry.

    Questions from the 3D scenarios

    Each answer is played out in the matching scenario above.

    No, only the bell rings. One zone in alarm only rings the bell. An automatic release needs a second zone to confirm, or someone to press the manual release.

    Turn the key to MANUAL ONLY. MANUAL ONLY blocks an automatic release while you are inside. The alarms keep working.

    Only one zone detected smoke. An automatic release needs both zones in alarm. One zone gives a first-stage alarm only.

    The countdown resumes and the gas is released. Hold-off works only while it is pressed and can never leave the system stopped on its own. Keep holding until MANUAL ONLY is keyed.

    On the panel, outside the door. The panel is outside the exit, so you release the gas without staying in the room. A separate release point is added only at other exits.

    Make sure the room is empty. The lever bypasses the panel and its countdown. The gas is released immediately.

    Choosing an agent, cost or maintenance? See the fire suppression FAQ

    Protect your server room

    Send us the room size and we will size the cylinders and the detection for you, and train your team on site.

    Request a quote Fire suppression services