Pressure Supervisory Switch (N/C) – UL Listed
The Pressure Supervisory Switch part CP50138-1 is used to monitor the pressure within the Clean Agent cylinder. If a cylinder leak occurs, and its pre
The Local Manual Control Head part CP61033 is used for manual actuation of the cylinder. It is made of solid Brass. It is self-venting with a safety
The Local Manual Control – UL Listed is part of the Clean Agent Fire Extinguishing Accessories range from Context Plus, supplied and supported by SPS. The Local Manual Control Head part CP61033 is used for manual actuation of the cylinder. It is made of solid Brass. It is self-venting with a safety pin to prevent accidental discharge. This Local Manual Control Head features a local lever driven push rod that depresses a Schrader check valve, thereby venting the pressure from the top of the piston in the cylinder valve, allowing the piston to slide upward and commence cylinder discharge.